PRN-5 Printer (Notifier, Firelite, Gamewell)

Prn5

PRN-5 Printer (Notifier, Firelite, Gamewell)


GENERAL
The PRN-5 printer is used with the NOTIFIER AM2020, AFP1010, AFC-600, AFP-400, AFP-300, AFP-00, AFP-100, NFS-640, and NFS-3030 fire alarm control panels to provide a written record of system events and status changes. The PRN-5 may also be used with the System 5000 or System 500 when used with the LCD-80 Liquid Crystal Display. When used with NOTIFIRENET, the PRN-5 may be used with the INA, NCA, NRT, or NCS.

FEATURES
Provides a hard-copy printout of all system events and status changes.
Time-stamps the printed record of each event and status change with the current time-of-day and date.
Uses standard 9" by 11" tractor-feed fan-fold paper.
Provides 80 columns of data at 10 characters per inch.
Provides printed record of system configuration and addressable device parameters.
Nine-pin print head.
Very quiet (approximately 55 dBA).

APPLICATIONS
Use with NOTIFIER NFS-3030, NFS-640, AM2020, AFP1010, AFC-600, AFP-400, AFP-300, AFP-200, AFP-100, System 5000, System 500, NRT, NCS, NCA, or INA. Printed transaction records reduce the man-hours required to install and maintain a system. A printed record of all system events (alarms,
troubles, etc.) and status changes can be especially valuable in the event of a disputed incident.

CONSTRUCTION AND OPERATION
The printer is housed in its own separate enclosure and is suitable for placement on a desk top, counter, or table.

INSTALLATION
The PRN-5 should be placed in a secure area to prevent theft of the printer and/or printed records.

The PRN-5 must not be located further than 50 ft./15.24 m (actual cable length) from the control panel.

The PRN-5 connects directly to the AFP-200 main PC board or AFP-300/AFP-400/AFC-600/NFS-640/NFS-3030 CPU board or to the Serial Interface Board (SIB-2048, SIB-2048A, SIB-NET, or SIB-232)
or the Display Interface Board (DIA-1010 or DIA-2020) in the AM2020 or AFP1010 control panel.

When used with the AFP-100, the PRN-5 connects to the PIM-24 option module.

When used with the INA, the PRN-5 can be connected directly within 50 feet (15.24 m).

When used with the System 5000 or System 500, the PRN-5 receives its information via the LCD-80 Liquid Crystal Display.

Messages programmed into the LCD- 80 nonvolatile memory will automatically be transmitted to the PRN-5 with a display of time and date.

The LCD-80 may be mounted in the System 5000 cabinet, or may be mounted remotely up to 6,000 feet (1828.8 m) from the cabinet.

When mounted remotely, the PRN-5 must be mounted within 50 ft. (15.24 m) of the LCD-80. On the NCS/NRT, the PRN-5 connects to the port.

Consult the control panel installation manual for the proper method and pin numbers used to complete the electrical connection to the control panel.

NOTE: If printer operation is required during failure of primary power, use of a separate UL-Listed Uninterruptable Power Supply (UPS) system is recommended.

PRINTER SPECIFICATIONS
Printing method: Serial printing with 9-pin matrix printhead.
Printing speed, high draft: 360 cps at 10 cpi.
Character density: 10 cpi standard (12, 15, 17.1, and 20 cpi available via front panel).
Graphic resolution (V x H): 144 x 240 dpi.
Ribbon life (approximate): 4 million characters (DPQ).
Acoustic noise level: 55 dBA (approximate).
Dimensions: 19" (48.26 cm) wide x 7.9" (20.07 cm) high x 9.7" (24.64 cm) deep.
Weight: 17.6 pounds (7.9 kg).
Power supply: 120/240 VAC.
Power consumption: 50 watts (operating).
Operating environment temperature: 50 F to 104 F (10 Cto 40 C).
Operating environment humidity: 20% to 80% (non-condensing).

PRODUCT LINE INFORMATION
PRN-5 9-pin, dot-matrix printer, 120 VAC power.