Honeywell PRN-7 Printer (Notifier, Firelite, Gamewell)

 
 
 
 


Prn 7 Cr




99003L Ribbons PRN7 2600, LA2600, 2600+, LA2600+
New
99003L 5-pack 9M Per ribbon (New)
$95.00



The PRN-7 printer is used with fire alarm control panels (FACPs) with printer capability to provide a written record of system events and status changes.

In NOTI-FIRE-NET applications, PRN-7 can be used with:

- - NCA-2
- - NCA
- - Onyxworks.

In the Gamewell-FCI applications, the PRN-7 can be used with:

- - E3 Series System
- - S3 Series System
- - 7100 Series System
- - 600 Series System

Features
- - Provides a hard copy printout of all system events and status changes.
- - Time stamps printed on the record of each event and status change with the current time-of-day and date.
- - Uses standard 9" x 11" tractor-feed fan-fold paper.
- - Provides 80 columns of data at 10 characters per inch.
- - Provides printed records of system configuration and addressable device parameters.
- - 24-pin print head.
- - Very quiet (approximately 52 dBA).

Applications
Printed transaction records reduce the man-hours required to install and maintain a system. A printed record of all system events (alarms, troubles, etc.) and status changes can be especially valuable in the event of a disputed incident.

Construction and Operation
The printer is housed in its own separate enclosure and is suitable for placement on a desk top, counter, or table.

Installation
The PRN-7 should be placed in a secure area to prevent theft of the printer and/or printed records.
The PRN-7 must not be located further than 20 ft/6.10 m (actual cable length) from the control panel.
Consult the control panel installation manual for the proper method and PIN numbers used to complete the electrical connection to the control panel.

NOTE: If printer operation is required during failure of primary power, use of a separate UL-listed Uninterruptable Power Supply (UPS) system is recommended.

Printer Specifications
Printer Method Serial printing with 24-pin matrix print head.
Printing Speed (copy draft) 333 cps at 10 cpi.
Character Density 10 cpi standard (12, 15, 17.1, and 20 cpi available via front panel).
Graphic Resolution (VxH) Up to 360 x 360 dpi.
Ribbon Life (approx.) 6 million characters (DPQ).
Acoustic Noise Level 52 dBA (approx.).
Dimensions 18" (45.8cm) W x 7.9" (20.01 cm) H x 10.4 (27.8cm) D.
Weight 18.9 pounds (8.6 kg).
Power Supply 110-230 VAC auto ranging, auto sensing.
Power Consumption 40 watts (printing).
Operating Environment Temperature 50F to 104F (10C to 40C).
Operating Environment Humidity 10% to 85% (non-condensing).

Agency Listings and Approvals
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

- - UL Listed: S35611
- - ULC Listed: E351188

Product Line Information
PRN-7: 24-pin dot-matrix printer, 110-230 VAC power.

For information on the proper method and PIN numbers required to complete the electrical connection to the fire alarm control panel, refer to the Gamewell-FCI module specific documentation located on the Gamewell-FCI Website, www.gamewell-fci.com.